A large office building experienced occupant comfort complaints and excessive compressor runtime across multiple air handling units.
The AHUs operated with a fixed SAT setpoint year-round, causing overcooling during light loads and unnecessary mechanical cooling.
Trend analysis was performed on SAT, RAT, OAT, VAV damper positions, and cooling valve output.
– Implemented dynamic SAT reset based on VAV demand – Raised SAT during low load periods – Added reset limits and safeguards
– Reduced compressor runtime by approximately 18% – Improved occupant comfort – Lowered reheat demand and energy consumption